RPFA913CE Pyro-electric Flame sensor

Zhengzhou Winsen Electronics Technology Stand: 4/C57

Application

  • It’s widely used in various oil storage stations, large warehouses, factory workshops, forests, charging piles; and standard configuration for high fire risk areas such as petroleum, chemical, paper-making, forests, and garages.
  • It also becomes popular in high-end residential, commercial, and general industrial fields.

Features

  • 4.4um detection band;
  • TO-5 package, single channel, voltage mode;
  • Low microphone effect, large FOV, high detection rate;
  • Detection band measurement of flame signal;

Specifications

ItemTypicalUnit
Window Size5.0*5.0mm
Sensitive element size3*3mm
Filter center wavelength4.4um
Electrical time constant5s
Thermal time constant200ms
Source Voltage0.4~0.7v
Working Voltage2~15v
Recommended voltage3~5v
Output signal V0 (500K,10HZ,25℃)4.5±10%v
Output noise voltage VN (10HZ, BW1HZ, 25℃)≤150mv
Voltage response rate (no window) Rv (500K, 10HZ, 25°C)≥500v/w
Specific detection rate (no window) D* (500K, 10HZ, BW1HZ, 25℃)≥5×108cmHz½/W
Field of view(FOV)>115°
Detection distance>35m
Working temperature/ Storage temperature-40~+85
Remarks: The magnification of the testing machine is 80dB.

* The description and specifications might be changed without notice. Please contact us for the latest information before placing orders.